It should be obvious that if you follow this method of compliance you will either have an incorrect number of audible appliances or an incorrect number of visible appliances.
Fire alarm strobe dimensions.
Design install a fire alarm in houston tx.
I will add if you are sizing boxes for fire alarm devices go big pushing horn strobes into place that could have eight 14 or 12 awg solid conductors connected to it is no joy if the box is tight.
Strobes must be installed no further than 100 feet apart down the length of a hallway.
Most contractors install strobe lights to comply with the national fire alarm and signaling code by simply using a combination audible visible appliance everywhere one or the other is shown on the plans.
6 where the ceiling strobe is not located in the center of the room the candela level shall be determined by doubling the distance from the appliance to the farthest wall to obtain the maximum room size.
5 intensity dependent upon room size.
If a corridor turns it must have strobe lights at each end so they can be seen from either direction.
Strobes must be located within 15 feet of either end of a hallway.
If there are 1000 plus rooms there should be 20 fire alarm strobe equipped rooms plus 1 additional equipped room for each 100 over 1000.
For hotels with 501 to 1000 rooms 2 percent of the rooms must be equipped with strobes.
Area to be ada ada ul 1971 ansi 117 1 nfpa 72 protected current anticipated anticipated requirement.